Backup power kit Deye 30 kW + Dyness STACK100 92.16 kWh, 2 towers, 3-phase

Three-phase high-voltage hybrid inverter Deye SUN-30K-SG01HP3-EU-BM3, 30 kW + Dyness STACK100 energy storage system 92.16 kWh (2 towers of 9 modules each): 18 × S51100 + 2 × SBDU100 + 2 × base.

Kit priceUAH 1,054,962excl. VAT
Contact us for availabilityA manager will confirm availability and lead time.

The price includes the inverter, 18 S51100 battery modules, 2 SBDU100 control units and 2 bases. The breaker cabinet with cables, installation and delivery are quoted separately.

Need a different capacity? All kits → Calculate autonomy in the calculator → Order installation: fill in the brief →
Get a quote with installation

Quick questions:

InverterDeye SUN-30K-SG01HP3-EU-BM3
Rated inverter power30 kW
Phases3
BatteryDyness STACK100: S51100 modules, LiFePO₄ 51.2 V / 100 Ah / 5.12 kWh
Number of modules18 × S51100
Battery configuration2 towers × 9 S51100 modules in parallel, 460.8 V nominal
Battery capacity92.16 kWh (rated, 18 × 5.12)
Installation space≈ 2.31 × 1.44 m (W × H)

How long will it run Комплект резервного живлення Deye 30 кВт + Dyness STACK100 92,16 кВт·год, 2 башти, 3 фази?

    Required capacity = load × time ÷ 0.855: we use 90 % of capacity as a reserve and 95 % conversion efficiency. Battery-side power = battery voltage × the inverter's battery-input current (manufacturer data). This is a guide, not a guarantee: inrush currents, temperature and settings are not included.

    A backup power kit for a three-phase home or business: a 30 kW Deye SUN-30K-SG01HP3-EU-BM3 hybrid inverter and a 92.16 kWh Dyness STACK100 high-voltage energy storage system. The battery is two towers of 9 S51100 modules each, every tower with its own SBDU100 control unit and base. The inverter has two independent battery inputs, so each tower can be connected to a separate input. Tower nominal voltage is 460.8 V, operating range 403–525 V; the inverter battery input range is 160–800 V.

    Calculated battery power based on the inverter battery input current: ≈46.08 kW (2 × 460.8 V × 50 A), not less than the inverter’s rated power. The name states the inverter’s rated power and the batteries’ nominal capacity. The available backup power depends on the battery configuration and equipment limits. The breaker cabinet with cables, installation and delivery are quoted separately.

    Features

    • Deye SUN-30K-SG01HP3-EU-BM3 three-phase hybrid inverter, 30 kW
    • Dyness STACK100: 92.16 kWh nominal capacity, 18 × S51100, 2 towers
    • Battery configuration: 2 towers × 9 S51100 modules in parallel, 460.8 V nominal
    • Battery power (calculated): ≈46.08 kW (2 × 460.8 V × 50 A)
    • LiFePO₄ modules, over 8,000 cycles, aerosol fire suppression in every module (Dyness data)
    • The price includes the inverter, modules, control unit and base; breaker cabinet with cables, installation and delivery are extra

    Kit contents

    ComponentPurposeQuantity
    Deye SUN-30K-SG01HP3-EU-BM3 hybrid inverterinverter1 pcs
    Dyness STACK100 S51100 battery module, 5.12 kWhbattery module18 pcs
    Dyness SBDU100 control unit with baseTower BMS (one per tower)2 pcs

    Not included in the price: the breaker cabinet with cables, installation and delivery. We select and quote these for your site.

    Technical specifications

    Kit contentsDeye SUN-30K-SG01HP3-EU-BM3 inverter × 1; Dyness S51100 modules, 5.12 kWh × 18; Dyness SBDU100 control unit with base × 2
    InverterDeye SUN-30K-SG01HP3-EU-BM3
    Rated inverter power30 kW
    Phases3
    Inverter typeHybrid, for high-voltage batteries
    Inverter battery voltage range160–800 V
    Inverter battery inputs2 independent
    Inverter battery charge / discharge current50 + 50 A (50 A per input)
    BatteryDyness STACK100: S51100 modules, LiFePO₄ 51.2 V / 100 Ah / 5.12 kWh
    Battery typeLiFePO₄, high-voltage (HV)
    Number of towers2
    Number of modules18 × S51100
    Control unit and baseDyness SBDU100 with base × 2 — one per tower; 134–876 V, up to 100 A
    Battery configuration2 towers × 9 S51100 modules in parallel, 460.8 V nominal
    Tower nominal voltage460.8 V
    Tower operating voltage403–525 V
    Battery capacity92.16 kWh (rated, 18 × 5.12)
    Usable energy (95% DoD)≈87.6 kWh in total
    Battery power (calculated)≈46.08 kW (2 × 460.8 V × 50 A) — not less than the inverter’s rated power
    Backup powerThe name states the inverter’s rated power and the batteries’ nominal capacity. The available backup power depends on the battery configuration and equipment limits.
    Not included in the priceBreaker cabinet with cables, installation and delivery

    Deye and Dyness manufacturer data. Please confirm the configuration before ordering.

    Installation space

    How much space the kit needs: the layout we use on our sites, clearances per the manufacturer’s manual. Approximate figures; the exact layout is agreed during the site visit.

    ≈ 2.31 m↕ ≈ 1.44 m
    Battery on the floor, inverter on the wall next to it, breaker box below the inverter (too tall to fit the inverter above the battery). Dashed areas are the manufacturer’s clearances.
    Layoutbattery on the floor, inverter on the wall next to it, breaker box below the inverter (too tall to fit the inverter above the battery)
    Width≈ 2.31 m; with the side clearances of the inverter ≈ 2.81 m
    Equipment height≈ 1.44 m
    Free wall height≈ 1.89 m
    Depth from the wall≈ 0.39 m + 1 m free access in front
    Floor area for batteries≈ 1.28 × 0.39 m
    Total equipment weight≈ 957 kg (batteries ≈ 877 kg)
    How the width is calculated2 × battery tower 590 + 100 between them + clearance 500 + inverter 527 = 2 307 mm; + clearance 500 = 2 807 mm
    How the height is calculatedbattery tower 1 435 + 200 free above the battery; breaker zone 500 (box 250 + 50 to battery and inverter; not less than the inverter’s bottom clearance 500) + inverter 894 + 500 free above the inverter; equipment 1 435 mm, with clearances 1 894 mm

    Clearances around the inverter: Deye manual: approx. 50 cm to the sides, above and below, 1 m in front. The size of the inverter’s breaker box (height 250 mm; a small box between inverter and battery, not the main panel), 50 mm from it to the battery and the inverter and 100 mm between battery columns are our assumptions for a typical installation, not manufacturer data. Equipment sizes and weights are from the manufacturers’ datasheets. Cable trays, room ventilation and floor load for heavy batteries are checked during the site visit. Dyness STACK100 tower height = base 100 + control unit 133.5 + modules of 133.5 mm each; the manufacturer requires 200 mm above the tower.

    Similar products

    Inverter30 kWBatteries81.92 kWh

    Inverter + battery kit

    Backup power kit Deye 30 kW + Dyness STACK100 81.92 kWh, 2 towers, 3-phase

    Three-phase high-voltage hybrid inverter Deye SUN-30K-SG01HP3-EU-BM3, 30 kW + Dyness STACK100 energy storage system 81.92 kWh (2 towers of 8 modules each): 16 × S51100 + 2 × SBDU100 + 2 × base

    • 30 kW
    • 81.92 kWh
    • 3 phases
    • 2 towers

    Suitable for: business

    Contact us for availability
    UAH 971,302 excl. VATDetails
    Inverter30 kWBatteries102.4 kWh

    Inverter + battery kit

    Backup power kit Deye 30 kW + Dyness STACK100 102.4 kWh, 2 towers, 3-phase

    Three-phase high-voltage hybrid inverter Deye SUN-30K-SG01HP3-EU-BM3, 30 kW + Dyness STACK100 energy storage system 102.4 kWh (2 towers of 10 modules each): 20 × S51100 + 2 × SBDU100 + 2 × base

    • 30 kW
    • 102.4 kWh
    • 3 phases
    • 2 towers

    Suitable for: business

    Contact us for availability
    UAH 1,138,622 excl. VATDetails
    Inverter30 kWBatteries71.68 kWh

    Inverter + battery kit

    Backup power kit Deye 30 kW + Dyness STACK100 71.68 kWh, 2 towers, 3-phase

    Three-phase high-voltage hybrid inverter Deye SUN-30K-SG01HP3-EU-BM3, 30 kW + Dyness STACK100 energy storage system 71.68 kWh (2 towers of 7 modules each): 14 × S51100 + 2 × SBDU100 + 2 × base

    • 30 kW
    • 71.68 kWh
    • 3 phases
    • 2 towers

    Suitable for: houses, business

    Contact us for availability
    UAH 887,642 excl. VATDetails
    Inverter30 kWBatteries112.64 kWh

    Inverter + battery kit

    Backup power kit Deye 30 kW + Dyness STACK100 112.64 kWh, 2 towers, 3-phase

    Three-phase high-voltage hybrid inverter Deye SUN-30K-SG01HP3-EU-BM3, 30 kW + Dyness STACK100 energy storage system 112.64 kWh (2 towers of 11 modules each): 22 × S51100 + 2 × SBDU100 + 2 × base

    • 30 kW
    • 112.64 kWh
    • 3 phases
    • 2 towers

    Suitable for: business

    Contact us for availability
    UAH 1,222,282 excl. VATDetails

    FAQ

    What is included in the kit?

    Three-phase high-voltage hybrid inverter Deye SUN-30K-SG01HP3-EU-BM3, 30 kW + Dyness STACK100 energy storage system 92.16 kWh (2 towers of 9 modules each): 18 × S51100 + 2 × SBDU100 + 2 × base. The breaker cabinet with cables, installation and delivery are quoted separately.

    What does the price include?

    Price: UAH 1,054,962 excl. VAT. The price includes the inverter, 18 S51100 battery modules, 2 SBDU100 control units and 2 bases. The breaker cabinet with cables, installation and delivery are quoted separately.

    Is the kit in stock?

    Contact us for availability: click "Request a quote" or leave a request, and a manager will confirm availability and lead time.

    How much power does the kit deliver from the battery?

    The name states the inverter’s rated power and the batteries’ nominal capacity. The available backup power depends on the battery configuration and equipment limits. Based on the inverter battery input current (50 + 50 A (50 A per input)), the calculated battery power is ≈46.08 kW (2 × 460.8 V × 50 A).

    How long will the kit power my site?

    It depends on the load. The battery’s nominal capacity is 92.16 kWh; the calculator on the "Kits" page will show the approximate runtime, or an engineer will calculate it in the quote.

    [→] — Request

    Calculation for a business

    Describe the site and the task: we will select the configuration, check compatibility and send a commercial proposal with the system composition.